Guides

Why more alarms do not make a VTS safer

Alarm floods hide the one alert that matters. What alarm-management standards say about alarm rates, and what that means for vessel traffic services.

Last checked 22 Oct 2026

An operator can act on only a few alarms at a time. Past that point, each new alarm hides the others. Alarm-management standards treat about one alarm per operator every ten minutes as acceptable, and ten or more in ten minutes as a flood [3, 4].

What alarm fatigue is

Alarm fatigue is what happens when alarms come too often, or when too many of them turn out to need nothing. People start to acknowledge alarms without reading them, to silence them, or to answer late. The real alarm then arrives inside a stream of false ones, and it gets the same treatment.

Ships know the problem. IMO's performance standard for bridge alert management sets out to harmonise how alerts are presented and handled on the bridge [2]. Its aim is that the bridge team can focus on safe operation and see at once which alerts need action.

What the standards measure

Refineries, chemical plants and power stations learned this lesson first, and wrote it down. EEMUA 191 and ANSI/ISA-18.2 are the reference documents for alarm management [3, 4]. The ISA standard defines an alarm as a signal to the operator of an abnormal condition that requires a timely response [4]. A signal that needs no response is not an alarm.

The two documents give benchmarks for a working alarm system [3, 4]:

Measure Benchmark
Average alarm rate for one operator About one in 10 minutes is very likely acceptable; about two is the most that can be managed
Alarm flood Ten or more alarms in 10 minutes for one operator
Priority mix Few at the top: roughly 5 % high priority, 15 % medium, 80 % low
Standing alarms Alarms left active for long periods should be rare

These numbers come from control rooms, not from traffic centres. They are still the best published yardstick for any job where one person watches a screen and must act on what it shows.

Why this applies to vessel traffic services

IMO defines a vessel traffic service as one with the capability to interact with traffic and respond to developing situations [1]. Its purpose is to mitigate the development of unsafe situations, partly by giving ships timely and relevant information [1]. Timely information depends on attention, and attention is the scarce part.

A busy strait shows why. Ferries, pilot boats and tugs work close to other ships all day, by design. A simple rule that raises an alarm whenever two ships pass close fires for each of them. At the busiest hour, such a rule can raise more alarms than any operator can read.

Quiet hours have the opposite problem. A rule tuned to stay quiet at rush hour can stay silent at night, when a slow and dangerous approach is the one that matters.

A fixed limit on distance or time therefore fails twice. It floods the operator when traffic is heavy, and it misses what matters when traffic is light. The answer is not a louder alarm or a lower limit. It is fewer alarms, each one worth reading.

What fewer, better alarms look like

The alarm-management standards agree on a few principles [3, 4]:

  1. Every alarm needs a defined response. If nobody would act on it, it should not be an alarm.
  2. Rank alarms by consequence. A tanker or a ship with dangerous cargo comes before a pleasure boat.
  3. Watch the rate at the busiest hour, not the daily average. Floods happen at the peak.
  4. Record every alarm that the system holds back, with its reason, and review those records.
  5. Measure the system against what really happened, and change it when it fails.

None of these principles asks the operator to work harder. They ask the system to do more of the sorting before anything reaches the screen.

Questions to ask of any alert system

  • How many alerts does one operator see in the busiest hour of a normal day?
  • What share of the alerts needed an action?
  • What does the system hold back, and is each held-back alert recorded with its reason?
  • Can a situation be replayed later, for review, investigation and training?
  • Was the system measured against real incidents and near misses in the waters it watches?

A system that cannot answer these questions has not been measured. A measured system makes its own trade-off between missed alarms and false ones visible, so the people responsible can judge it.

Sources

  1. Resolution A.1158(32), Guidelines for Vessel Traffic Services, 15 December 2021, International Maritime Organization (IMO).
  2. Resolution MSC.302(87), Adoption of performance standards for bridge alert management, International Maritime Organization (IMO).
  3. EEMUA Publication 191, Alarm systems: a guide to design, management and procurement, 4th edition, November 2024 (contents), Engineering Equipment and Materials Users Association (EEMUA).
  4. Getting the most from your safety alarms (on ANSI/ISA-18.2, Management of Alarm Systems for the Process Industries), International Society of Automation (ISA), InTech.